  • Product Name :

    TS-LSC3 Lightning Strike Recorder

  • Instruction

    TS-LSC3 lightning strike recorder is designed for easy mounting on a down conductor to effectively count the number of lightning strikes captured by the TSTLP E.S.E lightning arrester or surge arrester.TS-LSC3 measures lightning strikes by the induction of current and does NOT require the use of any external power source.

    ♦ Product Size

    TS-LSC3-Lightning-Strike-Recorder-Supplier


    TS-LSC4 Lightning Strike Recorder with NEW sensor to connect with Multiple Earthing Cables

    TS-LSC4-Lightning-Surge-Counter-Supplier


    ♦  Technical Data

    TSTLP  Model Nr 

    TS-LSC3

    Power Supply

    3V battery, Type CR123A, Exchangeable

    Min count current

    > 1KA, rise time 8~10μs

    Sequence of impulse

    > 1s

    LCD indicator

    3-digit(0~999)

    Inductive line

    1m long Twisted-pair

    Service life of battery

    ≥ 2 years (Do NOT pull the Insulated part before use)

    Enclosure material

    Black thermoplastic, UL94-V0

    Installation

    Mount on 35mm Din rail or inside waterproof box

    Dimension

    1.5 mods

    Certification

    CE(EMC, LVD)

     

    ♦  Installation Instruction :

     TS-LSC3 lightning strike recorder should be installed at a position along the down conductor(or PE Line) length where it can be accessed easily for inspection. Typically TS-LSC3 should be installed approximately 2 m from ground level or alternatively within the earth pit at the lower termination point of the down conductor(copper cable).

      When installing the TSTLP lightning stroke recorder the following should be considered:

      • TS-LSC3 lightning stroke recorder should be mounted away from areas where damage may occur due to theft,vandalism or nearby operations.

      • TS-LSC3 lightning stroke recorder can be enclosed in a security enclosure but the display should be kept visible to allow for the checking of recorded strikes. 

    ♦ Installation Diagram - 1