Lightning Surge Counter
Instruction
TS-LSC3 lightning strike recorder is designed for easy mounting on a down conductor to effectively count the number of lightning strikes captured by the TSTLP E.S.E lightning arrester or surge arrester.TS-LSC3 measures lightning strikes by the induction of current and does NOT require the use of any external power source.
♦ Product Size
TS-LSC4 Lightning Strike Recorder with NEW sensor to connect with Multiple Earthing Cables
♦ Technical Data
TSTLP Model Nr |
TS-LSC3 |
Power Supply |
3V battery, Type CR123A, Exchangeable |
Min count current |
> 1KA, rise time 8~10μs |
Sequence of impulse |
> 1s |
LCD indicator |
3-digit(0~999) |
Inductive line |
1m long Twisted-pair |
Service life of battery |
≥ 2 years (Do NOT pull the Insulated part before use) |
Enclosure material |
Black thermoplastic, UL94-V0 |
Installation |
Mount on 35mm Din rail or inside waterproof box |
Dimension |
1.5 mods |
Certification |
CE(EMC, LVD) |
♦ Installation Instruction :
TS-LSC3 lightning strike recorder should be installed at a position along the down conductor(or PE Line) length where it can be accessed easily for inspection. Typically TS-LSC3 should be installed approximately 2 m from ground level or alternatively within the earth pit at the lower termination point of the down conductor(copper cable).
When installing the TSTLP lightning stroke recorder the following should be considered:
• TS-LSC3 lightning stroke recorder should be mounted away from areas where damage may occur due to theft,vandalism or nearby operations.
• TS-LSC3 lightning stroke recorder can be enclosed in a security enclosure but the display should be kept visible to allow for the checking of recorded strikes.
♦ Installation Diagram - 1