Early Streamer Emission Air Terminal
Home » Lightning Products » Early Streamer Emission Air Terminal
Previous : SMT-ESE40 lightning Arrester
Next : SMT-ESE60 Lightning Rod
Instruction
Superior G3 TSTLP® Early Streamer Emission Lightning Conductor (referred as Ese Lightning Conductor) is designed according to the most popular standard NF C 17-102:2011 Annexe C for structure WIDER lightning protection system
|
KEY BENEFITS OF SMT-ESE50 1, PATENT Available 2, Latest French standard NF C 17-102:2011 Annexe C as well as UNE 21.186:2011 Paragraph C Compliant 3, CE marking 4, Fully Autonomous Operation 5, TSTLP® ESE lightning conductor only becomes active when electrical field intensity rises(lightning discharge likely), TSTLP® ESE lightning conductor presents no danger to the site. 6, Totally reliability, even in extreme climatic conditions. 7, Robust to withstand multiple lightning strikes. 8, ISO 9001:2015 Certified Manufacturing & Operating Process |
Working Principle of TSTLP® Early Streamer Emission ESE lightning conductor Check Flash Video at http://youtu.be/wxpmdJ9BBRk |
Comparing TSTLP® ESE lightning conductor with ordinal lightning conductor |
TSTLP® SMT-ESE50 EARLY STREAMER EMISSION LIGHTNING CONDUCTOR (E.S.E) |
|||||
CHARACTERISTICS |
|||||
Efficiency (ΔT) |
50μs |
||||
ΔL |
50M |
||||
Standard Deviation ESE / Single Rod σ |
σESE < 0.5 σPTS |
||||
Lightning current withstanding test - Iimp |
100kA (normative test at 10/350μs waveform as standard requires) |
||||
Lightning current withstanding - Iimp |
≥ 200KA (10/350 μs) |
||||
Capacity against wind speed |
≥40 m/s |
||||
Approx net weight |
4.0 kgs |
||||
Size
|
|||||
OPERATING PRINCIPLES |
|||||
Detection of downward leader |
Continuous measuring of electric field gradient (ΔE/Δt) |
||||
Upward streamer development conditions |
TSTLP®-SMART Technology optimizing the streamer development conditions |
||||
Upward streamer emission |
Sparking by High Voltage Impulses |
||||
Internal circuits |
4 Independent working unit |
||||
Central rod |
Full electrical continuity |
||||
Metal housing |
Superior Stainless Steel |
||||
On-site testing capabilities |
Proprietary E.S.E. tester |
||||
Maintenance |
Free (thanks to TSTLP advanced technology & superior material) |
||||
Warranty |
10 years |
||||
MECHANICAL SPECIFICATIONS |
|||||
Fixing on pole |
M20 Thread |
||||
Down conductor connection |
Specific clamp |
||||
PACKING |
|||||
Dimensions |
230*230*450mm colorful box/pc, 4pc boxes in 480*490*490mm carton |
||||
Contents |
1- TSTLP® E.S.E. Head; 2- Nut; 3- Hex key; 4- NEW Adapter |
||||
Approx Gross Weight |
5.0 kg |
||||
Environmental sustainability |
100% recyclable |
||||
CERTIFICATIONS |
|||||
Patent Right |
No. 2013300191397 |
||||
CE Marking |
No. WTS16030019S |
||||
COMPLIANCE |
|||||
Reference Standards |
NF C 17-102:2011 Annexe C UNE 21.186:2011 Paragraph C UNE-EN 62561 UNE-EN 60068-2-52 UNE-EN ISO 6988
NP4426-2 IEC 60060-1:2010 Part 1 EN / IEC 62305 EN 60060-1:2010 GB/T T16927.1-2011 Part 1 |
||||
PROTECTION RADIUS The protection radius of TSTLP® ESE lightning conductor is related to its height (h) relative to the surface to be protected, to its efficiency and to the selected protection level for h ≥ 5 m; and Rp = h × Rp(5)/5 for 2 m ≤ h ≤ 5 m Rp (h) (m): is the protection radius at a given height h h (m) : is the height of the ESE lightning conductor tip over the horizontal plane through the furthest point of the object to be protected r (m) : 20 m for protection level I 30m for protection level II 45m for protection level III 60m for protection level IV Δ (m) = ΔT x 106 Field experience has proved that Δ is equal to the efficiency obtained during the ESE lightning conductor evaluation tests |
|||||
PROTECTION LEVELS |
|||||
Protection Level |
Level I (99%, D=20m) |
Level II (97%, D=30m) |
Level III (91%, D=45m) |
Level IV (84%, D=60m) |
|
TSTLP® Model |
SMT-ESE50 |
||||
Delta T (ΔT) |
50μs |
||||
h(m) |
RADIUS PROTECTION (m) |
||||
2 |
27 |
30 |
34 |
38 |
|
3 |
41 |
46 |
52 |
57 |
|
4 |
54 |
61 |
69 |
76 |
|
5 |
68 |
76 |
86 |
95 |
|
6 |
69 |
76 |
87 |
96 |
|
8 |
69 |
77 |
87 |
97 |
|
10 |
69 |
77 |
88 |
98 |
|
12 |
70 |
78 |
89 |
99 |
|
20 |
70 |
79 |
92 |
102 |
|
30 |
/ |
80 |
94 |
106 |
|
45 |
/ |
/ |
95 |
109 |
|
60 |
/ |
/ |
/ |
110 |
See more overseas references @ http://www.tslpro.com/references-4.html |