Type 1+2 Lightning Current Arrester
Home » Lightning Products » Power Supply Surge Protection » Type 1+2 Lightning Current Arrester
Instruction
TS Series Type 1 & 2 Surge Protection is designed to protect low voltage devices from surge damages, specially designed for TN-S or TT system. Mainly used in power supply system such as power distribution-room,distribution-cabinet and other important power supply system. Designed according to IEC61643-11 & GB 18802.11.
♦ Basic Circuit Diagram
♦ Basic Circuit Diagram
♦ Technical Data of TS-385BC25
Model Number 4+0 for TN-S system; 3+0 for TN-C system 2+0 for TN system 3+1 for TN-S/TT system 1+1 for TN/TT system |
TS-385BC25/4 TS-385BC25/2 TS-385BC25 (4+0,2+0, 1P) |
TS-385BC25/4 TS-385BC25/2 TS-385BC25 (3+1, 1+1, N-PE) |
||
Rated voltage (max. continuous voltage) |
Uc |
385 VAC~ |
385 VAC~ |
|
Lightning impulse current (10/350) |
Iimp |
100kA (total) |
100kA (total) |
|
Lightning impulse current (10/350) |
Iimp |
25kA |
25kA (L-N) |
100kA(N-PE) |
Nominal discharge current (8/20) |
In |
100kA |
100kA |
|
Max. discharge current (8/20) |
Imax |
120kA |
120kA |
|
Voltage protection level |
Up |
≤ 2.0kV |
≤ 2.0kV(L-N) |
≤1.5kV(N-PE) |
Follow current extinguishing capability at Uc |
If |
32A fuse will not be triggered at 2kArms (L-N) |
32A fuse will not be triggered at 2kArms (L-N) |
100Arms (N-PE) |
Response time |
tA |
≤ 100ns |
≤ 100ns |
|
TOV voltage |
UT |
440V/120min (L-N) |
440V/120min (L-N) |
1200V/200ms |
Max. back up fuse (L) |
|
200AgL/gG |
||
Max. back up fuse (L-L’) |
|
125AgL/gG |
||
Operating temperature range (parallel wiring) |
TUP |
-40°C...+80°C |
||
Operating temperature range (through wiring) |
TUS |
-40°C...+60°C |
||
Relative humidity: |
|
≤95% (25°C) |
||
Cross-sectional area |
|
35mm2 solid / 50mm2 flexible |
||
Mounting on |
|
35mm DIN rail |
||
Enclosure material |
|
Black thermoplastic, UL94-V0 |
||
Dimension | 8 mods | |||
Standards |
|
IEC 61643-11; GB 18802.11 |
♦ Technical Data of TS-255BC25
Model Number 4+0 for TN-S system 3+0 for TN-C system 2+0 for TN system 3+1 for TN-S/TT system 1+1 for TN/TT system |
TS-255BC25/4 TS-255BC25/2 TS-255BC25 (4+0,2+0, 1P) |
TS-255BC25/4 TS-255BC25/2 TS-255BC25 (3+1, 1+1, N-PE) |
|||
Rated voltage (max. continuous voltage) |
Uc |
255VAC~ |
255VAC~ |
||
Lightning impulse current (10/350) |
Iimp |
100kA (total) |
100kA (total) |
||
Lightning impulse current (10/350) |
Iimp |
25kA |
25kA (L-N) |
100kA(N-PE) |
|
Nominal discharge current (8/20) |
In |
100kA |
100kA |
||
Max. discharge current (8/20) |
Imax |
120kA |
120kA |
||
Voltage protection level |
Up |
≤ 1.8 kV |
≤ 1.8 kV(L-N); |
≤1.5 kV(N-PE) |
|
Follow current extinguishing capability at Uc |
If |
32A fuse will not be triggered at kArms (L-N) |
32A fuse will not be triggered at kArms (L-N) |
100Arms (N-PE) |
|
Response time |
tA |
≤ 100ns |
≤ 100ns |
||
TOV voltage |
UT |
335V / 5sec (L-N); |
335V / 5sec (L-N); |
600V/200ms |
|
Max. back up fuse (L) |
|
200AgL/gG |
|||
Max. back up fuse (L-L’) |
|
125AgL/gG |
|||
Operating temperature range (parallel wiring) |
TUP |
-40°C...+80°C |
|||
Operating temperature range (through wiring) |
TUS |
-40°C...+60°C |
|||
Relative humidity: |
|
≤95% (25°C) |
|||
Cross-sectional area |
|
35mm2 solid / 50mm2 flexible |
|||
Mounting on |
|
35mm DIN rail |
|||
Enclosure material |
|
Red thermoplastic, UL94-V0 |
|||
Dimension | 8 mods | ||||
standards |
|
IEC 61643-11; GB 18802.11 |
♦ MAIN CHARACTER
1, Combined Surge Protection for three-phase TN /TT system
2, Adopt hermetical GDT technology, high follow current extinguish capacity
3, Extremely low voltage protection
4, Double terminals for parallel or series (V-shape) connection
5, Multifunctional connection for conductor and busbars
INSTALLATION INSTRUCTION According to lightning protection zones concept, for installed at LPZ 0 -1 or higher. This surge protection is usually A installed in distribution-box or feeder bus of UPS, protecting devices or equipment downstream. Fuse must be installed at the upstream of the Surge Protection or the lightning arrester to make sure that protected system has double protection. The value of the fuse used in a Surge Protection system should be conformed to: 1. The value of FUSE should not be larger than the max.withstand capacity of the Surge Protection's backup fuse value. 2. Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited. Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of Surge Protection. |
INSTALLATION STEPS a. Mount the Surge Protection on 35 mm DIN rail. b. Connect conductors, the cross-sectional area of cable (L-N) must be larger than 16mm2 , and the earthing cable(N-PE) larger than 25mm2 . The withstand voltage value of cable is not smaller than AC500V; ensure wiring reliable. c. After above, switch on the power supply and turn on the circuit breaker, test the Surge Protection does not fault appear, this indicates the unit is operating normally. Regularly inspect the operating status, especially after lightning. Once the fuse upstream break, or the Surge Protection’s fault appear, electrician should check/replace the SPD. |
|
WARNING: 1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2. It is recommended that installation should be done under power off condition. |