Coaxial Surge Arrester
Home » Lightning Products » IT Surge Protection » Coaxial Surge Arrester
Previous : TS-BNC5 Coaxial Surge Arrester
Instruction
♦ TS-8BNC5 Coaxial Surge Protection Device is designed according to IEC 61643-21; GB 18802.21; YD/T 1542 for protecting coaxial cable transmission devices from interruption caused by surge current, surge protection for up to 8pcs BNC connection, provide reliable protection for coaxial cable transmission devices or video signal transmission devices from surge, operating over voltage and electrostatic.
♦ Product Size
♦ Basic Circuit Diagram(TS-8BNC5)
♦ Technical Data
Model |
|
TS-8BNC5 |
Nominal voltage |
Un |
5V- |
Rated voltage (max. continuous voltage) |
Uc |
8V- |
Lightning Impulse Current (10/350) |
Iimp |
0.5KA |
Nominal discharge current (8/20) |
In |
2.5kA(line-shield) 5kA(shield-PG) |
Max. discharge current (8/20) |
Imax |
5kA(line-shield) 10kA(shield-PG) |
Voltage protection level at In |
Up |
≤25V(line-shield) |
Voltage protection level at 1kV/µs |
Up |
≤15V(line-shield) ≤600V(line/shield-PG) |
Response time |
tA |
≤1ns (line- shield) ≤100ns (shield-PG) |
Bandwidth |
fG |
300MHz |
Max. data transmission rates |
Vs |
16Mbits/s |
Operating temperature range |
|
-40°C ~ +80°C |
Relative humidity |
|
≤ 95% (25°C) |
Connection (input / output) |
|
BNC(socket/plug) |
Mounting on |
|
distribution cabinet |
Earthing via |
|
Earthing screw |
Shield earthing |
|
Indirectly via integrated spark gap |
Standards |
|
IEC 61643-21; GB 18802.21; YD/T 1542 |
Certification |
|
CE(LVD,EMC) |
♦ MAIN CHARACTER
INSTALLATION INSTRUCTION 1. This Coaxial Surge Protection Device is connected in series to the protected device. 2. The out terminal should be connected to the protected devices. 3. Coaxial Surge Protection Device's earthing terminal must be connected to nearby earthing Busbar or the metal earthing enclosure of protected device. Regularly inspect the operating status, especially after lightning, once the communication is off, electrician should check/replace the Coaxial Surge Protection Device. |
INSTALLATION DIAGRAM |
WARNING: 1, The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2, It is recommended that installation should be done under power off condition. |