Type 1 Lightning Current Arrester
Home » Lightning Products » Power Supply Surge Protection » Type 1 Lightning Current Arrester
Previous : TS-385B25RM/4 Class B Surge Protector
Instruction
TS Series Class 1 Surge Suppression Device is designed for installation at LPZ 0A -1 or higher, protecting low voltage equipment against lightning and surge damages. Applied in surge suppression devices class b for various power supply system. Designed according to GB 18802.11 / IEC 61643-11
♦ Product Size
♦ Basic Circuit Diagram (L-N):
♦ Basic Circuit Diagram (N-PE):
♦ Technical Data of TS-385B25RM
Model Number |
TS-385B25RM |
|
Rated voltage (max. continuous voltage) |
Uc |
385 VAC~ |
Lightning impulse current (10/350) |
Iimp |
25 KA |
Nominal discharge current (8/20) |
In |
50 KA |
Max. discharge current (8/20) |
Imax |
100KA |
Voltage protection level |
Up |
≤ 2.5 kV |
Follow current extinguishing capability at Uc |
If |
32A fuse will not be triggered at 2kArms |
Response time |
tA |
≤ 100ns |
TOV voltage |
UT |
335V / 5sec |
Max. back up fuse (L) |
|
200AgL/gG |
Max. back up fuse (L-L’) |
|
125AgL/gG |
Operating temperature range (parallel wiring) |
TUP |
-40°C...+80°C |
Operating temperature range (through wiring) |
TUS |
-40°C...+60°C |
Relative humidity: |
|
≤95% (25°C) |
Cross-sectional area |
|
35mm2 solid / 50mm2 flexible |
Mounting on |
|
35mm DIN rail |
Enclosure material |
|
Grey/Red thermoplastic, UL94-V0 |
standards |
|
IEC 61643-11; GB 18802.11 |
Certification |
|
CE (LVD, EMC) |
♦ Technical Data of TS-255B25RM
Model Number |
TS-255B25RM |
|
Rated voltage (max. continuous voltage) |
Uc |
255 VAC~ |
Lightning impulse current (10/350) |
Iimp |
25 KA |
Nominal discharge current (8/20) |
In |
50 KA |
Max. discharge current (8/20) |
Imax |
100KA |
Voltage protection level |
Up |
≤ 2.2 kV |
Follow current extinguishing capability at Uc |
If |
32A fuse will not be triggered at 2kArms |
Response time |
tA |
≤ 100ns |
TOV voltage |
UT |
335V / 5sec |
Max. back up fuse (L) |
|
200AgL/gG |
Max. back up fuse (L-L’) |
|
125AgL/gG |
Operating temperature range (parallel wiring) |
TUP |
-40°C...+80°C |
Operating temperature range (through wiring) |
TUS |
-40°C...+60°C |
Relative humidity: |
|
≤95% (25°C) |
Cross-sectional area |
|
35mm2 solid / 50mm2 flexible |
Mounting on |
|
35mm DIN rail |
Enclosure material |
|
Red thermoplastic, UL94-V0 |
standards |
|
IEC 61643-11; GB 18802.11 |
Certification |
|
CE (LVD, EMC) |
♦ INSTALLATION INSTRUCTION
According to lightning protection zones concept, for installation at LPZ 0A -1 or higher. It is usually installed in floor distribution-box or ClassⅠmain distribution-box
Fuse must be installed at the upstream of the Lightning Current Arrester or the lightning arrester to make sure that protected system has double protection. The value of the fuse used in a Lightning Current Arrester system should be conformed to:
1. The value of FUSE should not be larger than the max.withstand capacity of the Lightning Current Arrester's backup fuse value.
2. Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.
Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of Lightning Current Arrester.
♦ INSTALLATION STEPS
1) Check the product for integrity of the package; make sure the product window indicates green.
2) Mount the Lightning Current Arrester on 35 mm DIN rail.
3) Connect conductors, the cross-sectional area of cable must be larger than 16mm2 . The withstand voltage value of cable is not smaller than AC500V; ensure wiring reliable.
4) If need remote alarm, it should be connected signal lines to remote signal terminal 1 and 2, or 2 and 3 (When normal, 1 and 2 open, 2 and 3 close; when fault, the state is reversed).
5) After above, switch on the power supply and turn on the circuit breaker, if the Lightning Current Arrester’s window does not appear red, this indicates the unit is operating normally.
Regularly inspect the operating status, especially after lightning. Once the fuse upstream break, or the Lightning Current Arrester’s fault appear, electrician should check/replace theLightning Current Arrester.
♦ MAIN CHARACTER
1, Single Pole surge suppression device, pluggable
2, Adopted hermetical GDT technology, high follow current extinguish capability
3, Extremely low voltage protection level
4, Double terminals for parallels or series(V-shape) connection.
5, Multiple connection for conductors and busbars.
6 Green windows will change to Red when fault occurs and remote alarm terminal available at the same time.
♦ Installation Diagram
♦ WARNING:
1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations.
2. It is recommended that installation should be done under power off condition.