TV Surge Arrester
Home » Lightning Products » IT Surge Protection » TV Surge Arrester
Instruction
♦ TS-CTV24 Satellite TV Surge Protector is designed according to IEC 61643-21; GB 18802.21; YD/T 1542 and apply in 75Ω satellite and cable TV system.
♦ Product Size
♦ Basic Circuit Diagram
♦ Technical Data
Model |
|
TS-CSTV24 |
Rated voltage (max. continuous voltage) |
Uc |
24V- |
Nominal current |
IL |
2A |
Lightning Impulse Current (10/350) |
Iimp |
0.5KA |
Nominal discharge current (8/20) |
In |
2.5KA |
Voltage protection level at In |
Up |
≤300V (line-shield) |
Voltage protection level at 1kV/ms |
Up |
≤60V (line-shield) |
Frequency range |
F |
5-3000MHz |
Insertion loss |
aE |
1.2dB (5-862MHz) 1.4dB (862-2400MHz) 2dB (2400-3000MHz) |
Return loss (input/output) |
aR |
≥ 14dB (5-47MHz) ≥ 18dB (47-3000MHz) |
Shield attenuation |
aS |
≥ 85dB (5-300MHz) ≥ 80dB (300-470MHz) ≥ 75dB (470-1000MHz) ≥ 55dB (1000-3000MHz) |
Surge impedance |
Z |
75Ω |
Response time |
R |
≤ 1ns (line-shield) |
Operating temperature range |
|
-40°C...+80°C |
Connection (input / output) |
|
F socket |
Shield earthing |
|
Screw terminal |
Mounting on |
|
35mm DIN rail |
Enclosure material |
|
Aluminum |
Standards |
|
IEC 61643-21; GB 18802.21; YD/T 1542 |
Certification |
|
CE(LVD,EMC) |
♦ MAIN CHARACTER
1, Good discharge capacity, low voltage protection level
2, Multiple protection, quick response, no interruption
3, F socket connection, easy for installation
INSTALLATION INSTRUCTION 1. This TV Surge Protector is connected in series to the protected device. 2. Mount the TV Surge Protector on 35 mm DIN rail. 3. The out terminal should be connected to the protected devices. 4. TV Surge Protector's earthing terminal must be connected to nearby earthing BusBar or the metal earthing enclosure of protected device. 5. After above, you should ensure the circuit is functioning. Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replace the TV Surge Protector.
|
INSTALLATION DIAGRAM |
WARNING: 1, The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2, It is recommended that installation should be done under power off condition. |