LSA-PLUS Surge Arrester
Home » Lightning Products » IT Surge Protection » LSA-PLUS Surge Arrester
Instruction
♦ TS Series LSA-PLUS telephone line surge protection is designed according to GB 18802.21 / IEC 61643-21,based on the LSA-PLUS wiring technology,easy for installation. it can provide surge voltage protection for one pairs of conductors or two single conductors. Mainly used for telephone system or measurement and control system.
♦ CUSTOM-MADE CIRCUIT、Voltage & Technical Data AVAILABLE
♦ Product Size
♦ Basic Circuit Diagram
♦ Technical Data
Model |
|
TS-DP1 LSA110 |
Nominal voltage |
Un |
110V- |
Rated voltage (max. continuous voltage) |
Uc |
180V- /126V~ |
Nominal current |
IL |
370mA |
Nominal discharge current (8/20) |
In |
5kA (per line) |
Voltage protection level at 1KV/µS |
Up |
≤ 250V (line-line) ≤ 600V (l ine-PG) |
Response time |
tA |
≤ 25ns (line-line) ≤ 100ns (line-PG) |
Bandwidth |
fG |
30MHz ( line - line ) |
Series impedance per line |
R |
4.7Ω |
Capacitance |
C |
≤ 0.2nF ≤ 15pF |
Relative humidity |
|
≤95% (25°C) |
Operating temperature range |
|
-40°C~ - +80°C |
Pluggable into |
|
LSA-PLUS disconnection block |
Earthing via |
|
Earthing BusBar |
Enclosure material |
|
Orange thermoplastic material , UL94-V0 |
Standards |
|
IEC 61643-21; GB 18802.21 |
Certification |
|
CE (LVD, EMC & RoHS) |
♦ MAIN CHARACTER
1, Good transmission
2, Decoupling resistance integrated
3, For installing at LPZ 0B-2 or higher
Installation instruction 1.The (telephone line) surge protection must be installed in correct direction. 2.Plug earthing BusBar into input terminal of LSA-PLUS disconnection block 3.Plug this product into the jack of LSA-PLUS disconnection block;make sure earthing terminal is contacted fully with earthing BusBar. Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replacethe SPD. |
Installation diagram |
WARNING: 1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2. It is recommended that installation should be done under power off condition. |