Antenna Surge Arrester
Home » Lightning Products » IT Surge Protection » Antenna Surge Arrester
Instruction
TS-G2500N Antenna Surge Arrester is for 50Ω coaxial system at LPZ0B-1;Designed according to IEC 61643-21; GB 18802.21; YD/T 1542. and applied to various feed system,and so on.
♦ Product Size [ TS-G2500N(90V) N connector ]

♦ Product Size [ TS-G3000N(250V) N connector ]
♦ Basic Circuit Diagram
♦ Technical Data
Model |
|
TS-G2500N |
TS-G2500N |
TS-G3000N |
Rated voltage (max. continuous voltage) |
Uc |
90V |
250V |
250V |
Nominal current |
IL |
--- |
3.5A |
3.5A |
Lightning impulse current(10/350) |
Iimp |
1KA |
1KA |
1KA |
Nominal discharge current (8/20) |
In |
5KA |
8KA |
8KA |
Max.discharge current (8/20) |
Imax |
--- |
20KA |
20KA |
Voltage protection level at Imax |
Up |
≤150V |
≤750V |
≤750V |
Frequency range |
F |
2500MHZ |
2500MHZ |
3000MHZ |
Max.output power |
p |
500W |
||
Insertion loss |
aE |
≤0.2dB |
||
Return loss(input/output) |
aR |
≥20dB |
||
Surge impedance |
Z |
50Ω |
||
Operating temperature range |
|
-40°C...+80°C |
||
Connection (input / output) |
|
N (socket/plug) |
||
Shield earthing |
|
Outgoing connecting port |
||
Enclosure material |
|
Aluminum |
||
Standards |
|
IEC 61643-21; GB 18802.21; YD/T 1542 |
||
Certification |
|
CE(LVD,EMC) |
♦ MAIN CHARACTER
1, Good discharge capacity, low voltage protection level
2, Quick response, no interruption
3, N head connection, easy for installation
INSTALLATION INSTRUCTION 1. This product is connected in series to the protected device. 2. The out terminal should be connected to the protected devices. 3. SPD's earthing terminal must be connected to nearby earthing BusBar or the metal earthing enclosure of protected device. 4. After above, you should ensure the circuit is functioning. Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replace the SPD.
|
INSTALLATION DIAGRAM (TS-G2500BNC & TS-G2500N) |
WARNING: 1, The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2, It is recommended that installation should be done under power off condition. |