    TS-230M5RM Class D Surge Protection Device

  • Instruction

    TS Series Type 3 Surge Protection Device is designed according to IEC 61643-11 / GB 18802.11 for installation at LPZ 1-2 or higher, protecting electronic equipment from surge damages. Applied in Surge Protective Device Class D for single-phase various power supply system.

    Similar & Related Power Supply Surge Protectors

    TS-230M5RM-Class-D-Surge-Protection-Device-Customized

    TS-230M5RM-Class-D-Surge-Protection-Device-Cheap

    TS-230M5RM-Class-D-Surge-Protection-Device-Professional

    ♦ Product Size

    TS-230M5RM-Class-D-Surge-Protection-Device-High-Efficiency

    ♦ Basic Circuit Diagram

    TS-230M5RM-Class-D-Surge-Protection-Device-Picture

    ♦ Technical Data

    Model Number

     

    TS-230M5RM 

    TS-120M5RM

    TS-60M5RM

    TS-48M2RM 

    TS-24M2RM 

    Normal a.c. Voltage

    Un

    230V

    120V

    60V

    48V

    24V

    Rated voltage (max.a.c. continuous voltage)

    Uc

    320V

    150V

    75V

    60V

    30V

    Rated voltage (max.d.c. continuous voltage)

    Uc

    320V

    150V

    75V

    60V

    30V

    Normal Current

    IL

    16A

    16A

    16A

    16A

    16A

    Nominal discharge current (8/20, L-N)

    In

    3KA

    2.5KA

    2.5KA

    1KA

    1KA

    Nominal discharge current (8/20, L+N-PE)

    In

    5KA

    5KA

    5KA

    2KA

    2KA

    Combination wave (L-N)

    Uoc

    6KV

    6KV

    6KV

    2KV

    2KV

    Combination wave (L+N-PE)

    Uoc

    10KV

    10KV

    10KV

    4KV

    4KV

    Voltage protection level(L-N)

    Up

    ≤1.15KV

    ≤0.7KV

    ≤0.5KV

    ≤0.35KV

    ≤0.2KV

    Voltage protection level(L+N-PE)

    Up

    ≤1.5KV

    ≤1.1KV

    ≤0.85KV

    ≤0.85KV

    ≤0.85KV

    Response time

    tA

    ≤25ns (L-N);   ≤100ns(L+N-PE)

    Max. back up fuse

     

    16A gL/gG

    Operating temperature range

    Tu

    -40°C...+80°C

    Short-circuit withstand capability at max.backup fuse

     

    6KArms

    Relative humidity:

     

    ≤95% (25°C)

    Cross-sectional area

     

    0.5mm2 ~ 6mm2 solid / 4mm2 flexible

    Mounting on

     

    35mm2 DIN rail

    Enclosure material

     

    Red thermoplastic, UL94-V0

    Standards

     

    IEC 61643-11; GB 18802.11

    Type of remote signalling contact

     

    Break contact

    Switching capacity

    UN/IN

    AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A

    Cross-sectional area for remote signalling contact

     

    Max. 1.5mm2 solid / flexible

    Certification

     

    CE (LVD, EMC)

     

     MAIN CHARACTER 
    1, High discharge capacity, quick response
    2, Green light indicates normal and red light indicates fault
    3, Single-phase protection and disconnector
    4, Remote signalling connector for fault indication

    ♦ INSTALLATION INSTRUCTION 

    According to lightning protection zones concept, for installation at LPZ 1-2 or higher. This surge protection device is usually installed in distribution-box, protecting electronic devices.

    Fuse must be installed at the upstream of the Surge Protection Device or the lightning arrester to make sure that the protected system has double protection. The value of the fuse used in a Surge Protection Device system should be conformed to:

    1.The value of FUSE should not be larger than the max. withstand capacity of the Surge Protection Device's backup fuse value.

    2.Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.

    3.Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of Surge Protection Device.

    ♦ INSTALLATION STEPS 

    1, Mount the Type 3 SPD on 35 mm DIN rail.

    2, Connect conductors, the cross-sectional area of cable must be larger than 4mm2 . The withstand voltage value of cable is not smaller than AC500V; ensure wiring reliable.

    3, If need remote alarm, it should be connected signal lines to remote signal terminal 1 and 2 connected.

    4, After above, switch on the power supply and turn on the circuit breaker, if the Surge Protection Device’s indicator light displays green,this indicates the unit is operating normally.

    Regularly inspect the operating status, especially after lightning. Once the fuse upstream breaks, or the Surge Protection Device's indicator light displays red, electrician should check/replace the Surge Protection Device. 

    ♦ INSTALLATION DIAGRAM

    TS-230M5RM-Class-D-Surge-Protection-Device-Picture


    TS-230M5RM-Class-D-Surge-Protection-Device-High-Quality

    ♦ WARNING:  

    1. The class 3 surge arrester must be installed by electrically skilled person, conforming to national standards and safety regulations.

    2. It is recommended that installation should be done under power off condition.