Type 1 Surge Arrester
Home » Lightning Products » Power Supply Surge Protection » Type 1 Surge Arrester
Previous : TS-385M60RM/4 Type 1 Surge Suppressor
Instruction
TS Series Single-Phase Type 1 Surge Protective Device is designed according to IEC 61643-11 / GB 18802.11. to protect low voltage devices from surge damages, mainly used in power supply system such as power distribution-room, distribution-cabinet and other important power supply system; widely used to protect mobile communication station, telecommunication center, airport, finance, and so on. For installation at LPZ 0A -1 or higher, applied in Surge Protective Device Type 1 for various power supply system.
♦ Product Size
♦ Basic Circuit Diagram(2+0)
♦ Basic Circuit Diagram(2+0)
♦ Technical Data of TS-385M60,50,40,30RM/2
Model Number
|
|
TS-385M60RM/2 (2P) |
TS-385M50RM/2 (2P) |
TS-385M40RM/2 (2P) |
TS-385M30RM/2 (2P) |
Rated voltage (max. continuous voltage) |
Uc |
385V~ |
385V~ |
385V~ |
385V~ |
Nominal discharge current (8/20) |
In |
60 KA |
50 KA |
40 KA |
30 KA |
Max. discharge current (8/20) |
Imax |
120 KA |
100KA |
80 KA |
60 KA |
Voltage protection level |
Up |
≤ 2.5KV |
≤ 2.2KV |
≤ 2KV |
≤ 1.8KV |
Response time |
tA |
≤ 25ns |
|||
Max. back up fuse (L) |
|
200AgL/gG |
|||
Max. back up fuse (L-L’) |
|
125AgL/gG |
|||
Operating temperature range |
Tu |
-40°C...+80°C |
|||
Relative humidity: |
|
≤95% (25°C) |
|||
Cross-sectional area |
|
35mm2 solid / 50 mm2 flexible |
|||
Mounting on |
|
35mm2 DIN rail |
|||
Enclosure material |
|
Grey/Red thermoplastic, UL94-V0 |
|||
Dimension |
|
8 mods |
|||
Standards |
|
IEC 61643-11 & GB 18802.11 |
|||
Type of remote signalling contact |
|
Switching contact |
|||
Switching capacity |
U/I |
AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A |
|||
Cross-sectional area for remote signalling contact |
|
Max. 1.5mm2 solid / flexible |
|||
Certification |
|
CE (LVD, EMC & RoHS) |
Model Number
|
|
TS-275M60RM/2 (2P) |
TS-275M50RM/2 (2P) |
TS-275M40RM/2 (2P) |
TS-275M30RM/2 (2P) |
Rated voltage (max. continuous voltage) |
Uc |
275V~ |
275V~ |
275V~ |
275V~ |
Nominal discharge current (8/20) |
In |
60 KA |
50 KA |
40 KA |
30 KA |
Max. discharge current (8/20) |
Imax |
120 KA |
100KA |
80 KA |
60 KA |
Voltage protection level |
Up |
≤ 2.2KV |
≤ 2.0KV |
≤ 1.8KV |
≤ 1.5KV |
Response time |
tA |
≤ 25ns |
|||
Max. back up fuse (L) |
|
200AgL/gG |
|||
Max. back up fuse (L-L’) |
|
125AgL/gG |
|||
Operating temperature range |
Tu |
-40°C...+80°C |
|||
Relative humidity: |
|
≤95% (25°C) |
|||
Cross-sectional area |
|
35mm2 solid / 50 mm2 flexible |
|||
Mounting on |
|
35mm2 DIN rail |
|||
Enclosure material |
|
Grey/Red thermoplastic, UL94-V0 |
|||
Dimension |
|
8 mods |
|||
Standards |
|
IEC 61643-11; GB 18802.11 |
|||
Type of remote signalling contact |
|
Switching contact |
|||
Switching capacity |
U/I |
AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A |
|||
Cross-sectional area for remote signalling contact |
|
Max. 1.5mm2 solid / flexible |
|||
Certification |
|
CE (LVD, EMC) |
♦ MAIN CHARACTER
♦ INSTALLATION INSTRUCTION
According to lightning protection zones concept, for installation at LPZ 0 -1 or higher. This Surge Protective Device is usually installed in distribution-box or feeder bus of UPS, protecting devices or equipment downstream. Fuse must be installed at the upstream of the Surge Protective Device or the lightning arrester to make sure that the protected system has double protection. The value of the fuse used in a Surge Protective Device system should be conformed to:
1. The value of FUSE should not be larger than the max withstand capacity of the Surge Protective Device's backup fuse value.
2. Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.
3. Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of Surge Protective Device.
♦ INSTALLATION STEPS
1) Check the product for integrity of the package; make sure the product window indicates green.
2) Mount the Surge Protective Device on 35 mm DIN rail.
3) Connect conductors, the cross-sectional area of cable must be larger than 16mm2 . The withstand voltage value of cable is not smaller than AC500V; ensure wiring reliable.
4) If need remote alarm, it should be connected signal lines to remote signal terminal 1 and 2, or 2 and 3 (When normal,1 and 2 open, 2 and 3 close; when fault, the state is reversed).
5) After above, switch on the power supply and turn on the circuit breaker,if the Surge Protective Device’s window does not appear red, this indicates the unit is operating normally.
Regularly inspect the operating status, especially after lightning. Once the fuse upstream break, or the Surge Protective Device's window indicates red, electrician should check/replace the Surge Protective Device
1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations.
2. It is recommended that installation should be done under power off condition.