• Product Name :

    TS-PV1000 Photovoltaic Surge Protector

  • Instruction

    TS-PV series DC Surge Protection Device for Solar Photovoltaicdesigned ccording to IEC 61643-11 / GB 18802.11. and is mainly applied in photovoltaic system, with three-step d.c. switching device, the max. PV voltage up to UCPV ≤ 1000V dc; protecting photovoltaic generator and inverter and so on. 

    Relative product TSTLP ESE Lightning Arrester for Solar Power Plant/Farm against direct lightning protection:

    TS-PV1000-Photovoltaic-Surge-Protector-Factory

    Relative Type 3 Surge Protector with AC/DC Surge Protection.

    TS-PV1000-Photovoltaic-Surge-Protector-Best-Price

    ♦ Product Size(3P)

    TS-PV1000-Photovoltaic-Surge-Protector-Widely-Used

    ♦ Product Size(2P)

    TS-PV1000-Photovoltaic-Surge-Protector-Factory

    ♦ Basic Circuit Diagram(3P)

    TS-PV1000-Photovoltaic-Surge-Protector-Manufacturer

    ♦ Basic Circuit Diagram(2P)

    TS-PV1000-Photovoltaic-Surge-Protector-Professional

    ♦ Technical Data 

    Model Number

     

    TS-PV1500RM

    TS-PV1000RM

    TS-PV600RM

    TS-PV150RM

    Max. PV voltage

    Uc pv

    ≤1500V

    ≤1000V

    ≤600V

    ≤150V

    Short-circuit current rating (EN50539-11)

    [ Iscpv ]

    1000A

    1000A

    1000A

    1000A

    Max. continuous d.c. voltage (DC+/DC- –› PE)

    Uc

    750V

    500V

    300V

    150V

    Normal discharge current (8/20) 

    In

    20 kA

    20 kA

    20 kA

    20 kA

    Max. discharge current (8/20) 

    Imax

    40 kA

    40 kA

    40 kA

    40 kA

    Voltage protection level at In

    Up

    ≤ 6 kV

    ≤ 4 kV

    ≤ 2.5 kV

    ≤ 0.8 kV

    Voltage protection level 5kA

    Up

    ≤ 5.2 kV

    ≤ 3.5 kV

    ≤ 2.0 kV

    ≤ 0.6 kV

    Response time

    tA

    ≤ 25ns

    Max. back up fuse (L)

     

    200A gL/gG

    Max. back up fuse (L-L’)

     

    125A gL/gG

    Operating temperature range

    Tu

    -40°C...+80°C

    Relative humidity:

     

    ≤95% (25°C)

    Cross-sectional area

     

    1.5mm2 ~ 25mm2 solid / 35mm2 flexible

    Mounting on

     

    35mm2 DIN rail

    Enclosure material

     

    Black thermoplastic, UL94-V0

    Standards

     

    IEC 61643-11 & GB 18802.11

    Type of remote signaling contact

     

    Switching contact

    Switching capacity

    UN/IN

    AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A

    Cross-sectional area for remote signalling contact

     

    Max. 1.5mm2 solid / flexible

    Compliance

     

    CE (LVD, EMC & RoHS)

     

     MAIN CHARACTER 

    1, High discharge capacity, quick response, pluggable
    2, Approved fault-resistant Y circuit, consist of three varistors and thermal disconnection devices
    3, Double thermal disconnection devices, provide more reliable protection
    4, Green window will change when fault occurs, also provide remote alarm terminal at the same time

     

    ♦ INSTALLATION INSTRUCTION

    This surge protector is usually installed in distribution-box, protecting PV system devices in photovoltaic generator circuit. Fuse must be installed at the upstream of the Surge Protector or the lightning arrester to make sure that the protected system has double protection. The value of the fuse used in a Surge Protector system should be conformed to:

    1. The value of FUSE should not be larger than the max. withstand capacity of the Surge Protector's backup fuse value.

    2. Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.

    3. Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of Surge Protector.

    ♦ INSTALLATION STEPS

    1. Check the product for integrity of the package; make sure the product window indicate green.

    2. Mount the Surge Protector on 35 mm DIN rail.

    3. Connect conductors, the cross-sectional area of cable must be larger than 6mm2 . The withstand voltage value of cable is not smaller than AC800V; ensure wiring reliable.

    4. If need remote alarm, it should be connected signal lines to remote signal terminal 1 and 2, or 2 and 3 (When normal 1 and 2 open, 2 and 3 close; when fault, the state is reversed).

    5. After above, switch on the power supply and turn on the circuit breaker, if the Surge Protector appeared green window, indicates the unit is operating normally.

    Regularly inspect the operating status, especially after lightning. Once the fuse upstream break, or the Surge Protector's window not indicate green, electrician should check/replace the Surge Protector.

     Installation Diagram (3P)

     TS-PV1000-Photovoltaic-Surge-Protector-In-China

     

     Installation Diagram (2P)

    TS-PV1000-Photovoltaic-Surge-Protector-Cheap

    ♦ WARNING:  

    1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 

    2. It is recommended that installation should be done under power off condition.