Network Surge Arrester
Home » Lightning Products » IT Surge Protection » Network Surge Arrester
Instruction
♦ TS-RJ45 series Single-Port Surge Protection Device for RJ45 Network Protection (CE Approval)
INTRODUCTION:TS-RJ45 Network Surge Protection Device is designed to protect network equipment from interruption caused by surge current according to IEC 61643-21; GB 18802.21; YD/T 15420. Mainly used for network equipment, e.g. Switch, router, HUB, modem and so on.
♦ Product Size
♦ Basic Circuit Diagram
♦ Technical Data
Model |
|
TS-RJ45/5/8 |
TS-RJ45/24/8 |
Nominal voltage |
Un |
5V |
24V |
Rated voltage (max. continuousdc voltage) |
Uc |
6V |
30V |
Rated voltage (max. continuousac voltage) |
Uc |
4.2V |
21.1V |
Lightning Impulse Current (10/350) |
Iimp |
0.5KA |
0.5KA |
Nominal discharge current (8/20) |
In |
0.3kA (line-line) 0.3kA (line-PG) 2.5kA (shield-PG) |
0.1kA (line-line) 0.1kA (line-PG) 2.5kA (shield-PG) |
Max. discharge current (8/20) |
Imax |
0.4kA (line-line) 0.4kA (line-PG) 5kA (shield-PG) |
0.2kA (line-line) 0.2kA (line-PG) 5kA (shield-PG) |
Voltage protection level at In |
Up |
≤35V (line-line) ≤35V (line-PG) |
≤60V (line-line) ≤60V (line-PG) |
Voltage protection level at 1kV/ms |
Up |
≤13V (line-line-PG) ≤700V (shield-PG) |
≤45V (line-line-PG) ≤700V (shield-PG) |
Response time |
tA |
≤1ns (line-line) ≤100ns (shield-PG) |
|
Bandwidth |
fG |
165MHz |
|
Max. data transmission rates |
Vs |
100Mbits/s |
|
Operating temperature range |
|
-40°C...+80°C |
|
Connection (input / output) |
|
RJ45 shield socket |
|
Pining |
|
1/2, 3/6, 4/5, 7/8 |
|
Earthing via |
|
Earthing screw |
|
Mounting on |
|
35mm DIN rail |
|
Enclosure material |
|
Aluminum |
|
Standards |
|
IEC 61643-21; GB 18802.21 |
|
Certification |
|
CE(LVD,EMC) |
♦ MAIN CHARACTER
1, For protecting computer data transmission system, network system and so on
2, Good discharge capacity, low voltage protection level
3, Quick response, high transmission speed, low signal attenuation
4, RJ45 connection, easy for installation
INSTALLATION INSTRUCTION 1. This network surge protection device is connected in series to the protected device. 2. Mount the SPD on 35 mm DIN rail. 3. The out terminal should be connected to the protected devices. 4. The Surge Protection Device's earthing terminal must be connected to nearby earthing BusBar or the metal earthing enclosure of protected device. Regularly inspect the operating status, especially after lightning.Once the communication is off, electrician should check/replace the Surge Protection Device. |
INSTALLATION DIAGRAM |
WARNING: 1, The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2, It is recommended that installation should be done under power off condition. |