Information Surge Arrester
Home » Lightning Products » IT Surge Protection » Information Surge Arrester
Previous : TS-ITS-ME5 RS422 Surge Protection
Instruction
♦ TS-RS485/5 Surge Suppression for Information Technology System
INTRODUCTION:TS-RS485/5 RS485 Surge Suppression is designed according to GB 18802.21 / IEC 61643-21 for installation at LPZ 0B -2 or higher.Provide surge current protection for RS 485/RS 422 industrial bus control,other field bus and temperature measurement.
♦ Product Size

♦ Basic Circuit Diagram

♦ Technical Data
|
Model |
|
TS-RS485/5 |
|
Nominal voltage |
Un |
5V- |
|
Rated voltage (max. continuous voltage) |
Uc |
6V- / 4.2V~ |
|
Nominal current |
IL |
0.5A |
|
Nominal discharge current (8/20) |
In |
10kA |
|
Voltage protection level at In |
Up |
≤ 20V (line-line) ≤ 700V (line-PG) |
|
Voltage protection level at 1KV/µs
|
Up |
≤ 8.5V (line-line) ≤ 600V (line-PG) |
|
Response time |
tA |
≤ 1ns (line-line) ≤ 100ns (line-PG) |
|
Bandwidth |
fG |
1.7MHz |
|
Series impedance per line |
R |
1.8Ω |
|
Capacitance |
C |
≤ 5nF |
|
Operating temperature range |
|
-40°C...+80°C |
|
Relative humidity: |
|
≤95% (25°C) |
|
Cross-sectional area |
|
Max. 2.5mm2 flexible |
|
Mounting on |
|
35mm DIN rail |
|
Enclosure material |
|
Yellow thermoplastic, UL94-V0 |
|
Standards |
|
IEC 61643-21; GB 18802.21 |
|
Certification |
|
CE (LVD, EMC) |
♦ MAIN CHARACTER
1, Quick response
2, Low voltage protection level
3, Direct or indirect shield earthing
|
INSTALLATION INSTRUCTION 1. This RS485 Surge Suppression is connected in series to the protected device. 2. The out terminal should be connected to the protected devices. 3. There is a earthing terminal at input side,earth lead must be connected to the lightning earthing system, ideally using 2.5mm² cable. The cable should be as short as possible. 4, Shields on the TS-RS485/5 can be grounded directly or indirectly.If grounded directly,the shield of the incoming cable is connected to terminal 8(IN) and the outgoing cable is connected to terminal 8´(OUT). If grounded directly,the shield of the incoming cable is connected to terminal 7(IN) and the outgoing cable is connected to terminal 7´(OUT). Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replacethe SPD.= |
|
TS-RS485/5 INSTALLATION DIAGRAM
|
|
WARNING: 1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2. It is recommended that installation should be done under power off condition. |