Information Surge Arrester
Home » Lightning Products » IT Surge Protection » Information Surge Arrester
Previous : TS-SP24 Information Surge Protector
Next : TS-SD5 Data Surge Arrester
Instruction
♦ TS-SC series Surge Protection Device for Information Technology System (CE Approval)
INTRODUCTION:TS-SC series surge protection device is designed according to IEC 61643-21 & GB 18802.21 and installed at LPZ 0B -2 or higher. Applied in measuring and controlling system, providing coarse and fine protection.
♦ CUSTOM-MADE CIRCUIT、Voltage & Technical Data AVAILABLE
♦ Product Size
♦ Basic Circuit Diagram
♦ Technical Data
Model |
|
TS-SC12 |
TS-SC24 |
TS-SC48 |
TS-SC110 |
Nominal voltage |
Un |
12V- |
24V |
48V |
110V |
Rated voltage (max. continuous voltage) |
Uc |
14V- / 9.5V~ |
33V-/ 23V~ |
55V-/ 38.5V~ |
170V-/ 120V~ |
Nominal current |
IL |
0.5A |
0.5A |
0.5A |
0.5A |
Nominal discharge current (8/20) |
In |
5kA (per line) 10kA (total) |
|||
Voltage protection level at In |
Up |
≤ 55V (line-line) ≤ 40V (line-PG) |
≤110V (line-line) ≤ 65V (line-PG) |
≤ 175V (line-line) ≤ 100V (line-PG) |
≤ 500V (line-line) ≤ 270V (line-PG) |
Voltage protection level at 1kV/µs |
Up |
≤ 36V (line-line) ≤ 19V (line-PG) |
≤ 90V (line-line) ≤ 45V (line-PG) |
≤ 160V (line-line) ≤ 80V (line-PG) |
≤ 460V (line-line) ≤ 230V (line-PG) |
Response time |
tA |
≤ 1ns (line-line) ≤ 1ns (line-PG) |
≤ 1ns (line-line) ≤ 1ns (line-PG) |
≤ 1ns (line-line) ≤ 1ns (line-PG) |
≤ 1ns (line-line) ≤ 1ns (line-PG) |
Bandwidth |
fG |
2.5MHz (line-PG) |
6MHz (line-PG) |
10MHz (line-PG) |
16MHz (line-PG) |
Series impedance per line |
R |
1.8Ω |
|||
Capacitance |
C |
≤ 1.2nF (line-line) ≤ 2.4nF (line-PG) |
≤ 0.5nF (line-line) ≤ 1nF (line-PG) |
≤ 0.3nF (line-line) ≤ 0.6nF (line-PG) |
≤ 0.2nF (line-line) ≤ 0.4nF (line-PG) |
Operating temperature range |
|
-40°C...+80°C |
|||
Cross-sectional area |
|
Max. 2.5m m2 flexible |
|||
Mounting on |
|
35mm DIN rail |
|||
Enclosure material |
|
Yellow thermoplastic, UL94-V0 |
|||
Standards |
|
IEC 61643-21; GB 18802.21 |
|||
Certification |
|
CE (LVD, EMC) |
♦ MAIN CHARACTER
1, Small size, only 6mm wide module
2, Connected to earth by DIN rail or earth terminal
INSTALLATION INSTRUCTION 1. This surge protection device is connected in series to the protected device. 2. Mount the SPD on the 35 mm DIN rail. 3. The out terminal should be connected to the protected devices. 4. There is a earthing terminal in each side, and it is recommended to use the one at output side,earth lead must be connected to the earthing system, ideally using 2.5mm² cable. The cable should be as short as possible. 5. After above, you should ensure the circuit is functioning. Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replace the SPD. |
TS-SC series INSTALLATION DIAGRAM
|
WARNING: 1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2. It is recommended that installation should be done under power off condition. |
- CONTACT US
- 0086 13926098193
- 0086 20 28819702 EXT 27806
- [email protected]
- Hongdiyuan Industrial Park, Wufeng Avenue, Linjiang Town, Jiangdong New District, Heyuan, Guangdong,P.R.C.
- http://www.tslpro.com
- +86 13926098193
- F13926098193
- tslpro.tstlp