• Product Name :

    TS-SC12 Data Surge Protection Device

  • Instruction

    ♦ TS-SC series Surge Protection Device for Information Technology System (CE Approval) 

    INTRODUCTION:TS-SC series surge protection device is designed according to IEC 61643-21 & GB 18802.21 and installed at LPZ 0B -2 or higher. Applied in measuring and controlling system, providing coarse and fine protection.

    ♦ CUSTOM-MADE CIRCUIT、Voltage & Technical Data AVAILABLE

    ♦ Product Size

    TS-SC12-Data-Surge-Protection-Device-Manufacturer


    ♦ Basic Circuit Diagram

    TS-SC12-Data-Surge-Protection-Device-Widely-Used

    ♦ Technical Data 

    Model

     

    TS-SC12 

    TS-SC24 

    TS-SC48 

    TS-SC110 

    Nominal voltage

    Un

    12V-

    24V

    48V

    110V

    Rated voltage (max. continuous voltage)

    Uc

    14V- /

    9.5V~

    33V-/

    23V~

    55V-/

    38.5V~

    170V-/

    120V~

    Nominal current

    IL

    0.5A

    0.5A

    0.5A

    0.5A

    Nominal discharge current (8/20)

    In

    5kA (per line)

    10kA (total)

    Voltage protection level at In

    Up

    ≤ 55V (line-line)

    ≤ 40V (line-PG)

    ≤110V (line-line)

    ≤ 65V (line-PG)

    ≤ 175V (line-line)

    ≤ 100V (line-PG)

    ≤ 500V (line-line)

    ≤ 270V (line-PG)

    Voltage protection level at 1kV/µs

    Up

    ≤ 36V (line-line)

    ≤ 19V (line-PG)

    ≤ 90V (line-line)

    ≤ 45V (line-PG)

    ≤ 160V (line-line)

    ≤ 80V (line-PG)

    ≤ 460V (line-line)

    ≤ 230V (line-PG)

    Response time

    tA

    ≤ 1ns (line-line)

    ≤ 1ns (line-PG) 

    ≤ 1ns (line-line)

    ≤ 1ns (line-PG)

    ≤ 1ns (line-line)

    ≤ 1ns (line-PG)

    ≤ 1ns (line-line)

    ≤ 1ns (line-PG)

    Bandwidth

    fG

    2.5MHz (line-PG)

    6MHz (line-PG)

    10MHz (line-PG)

    16MHz (line-PG)

    Series impedance per line

    R

    1.8Ω

    Capacitance

    C

    ≤ 1.2nF (line-line)

    ≤ 2.4nF (line-PG)

    ≤ 0.5nF (line-line) 

    ≤ 1nF (line-PG)

    ≤ 0.3nF (line-line)

    ≤ 0.6nF (line-PG)

    ≤ 0.2nF (line-line)

    ≤ 0.4nF (line-PG)

    Operating temperature range

     

    -40°C...+80°C

    Cross-sectional area

     

    Max. 2.5m m2  flexible

    Mounting on

     

    35mm DIN rail

    Enclosure material

     

    Yellow thermoplastic, UL94-V0

    Standards

     

    IEC 61643-21; GB 18802.21

    Certification

     

    CE (LVD, EMC)

     MAIN CHARACTER 

    1, Small size, only 6mm wide module

    2, Connected to earth by DIN rail or earth terminal

    INSTALLATION INSTRUCTION 

    1. This surge protection device is connected in series to the protected device.

    2. Mount the SPD on the 35 mm DIN rail.

    3. The out terminal should be connected to the protected devices.

    4. There is a earthing terminal in each side, and it is recommended to use the one at output side,earth lead must be connected to the earthing system, ideally using 2.5mm² cable. The cable should be as short as possible.

    5. After above, you should ensure the circuit is functioning.

    Regularly inspect the operating status, especially after lightning. Once the communication is off,  electrician should check/replace the SPD.

    TS-SC series INSTALLATION DIAGRAM 

     TS-SC12-Data-Surge-Protection-Device-Low-Price

    WARNING:  

    1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 

    2. It is recommended that installation should be done under power off condition.