• Product Name :

    TS-SD5 Data Surge Arrester

  • Instruction

    ♦ TS-SD series Data Surge Arrester Device for Information Technology System 

    INTRODUCTION:TS-SD Series Data Surge Arrester is for installation at LPZ 0B -2 or higher, protecting the RS-422/RS-485 devices against lightning and surge damages, providing coarse and fine protection.

    ♦ CUSTOM-MADE CIRCUIT、Voltage & Technical Data AVAILABLE

    ♦ Product Size

    TS-SD5-Data-Surge-Arrester-Cheap

    ♦ Basic Circuit Diagram(TS-SD5)

    TS-SD5-Data-Surge-Arrester-In-China


    ♦ Basic Circuit Diagram(TS-SD24)

    TS-SD5-Data-Surge-Arrester-High-Efficiency

    ♦ Technical Data 

    Model

     

    TS-SD5 

    TS-SD24 

    Nominal voltage

    Un

    5V-

    24V-

    Rated voltage (max. continuous voltage)

    Uc

    6V(line/line)    160V(line/PG,SG/PG)

    6V(line/SG)

    32V(line/line)    160V(line/PG,SG/PG)

    32V(line/SG)

    Nominal discharge current (8/20)

    In

    10 KA

    10 KA

    Max. discharge current(8/20)

    Imax

    20 KA

    20 KA

    Lightning discharge current (10/350)

    Iimp

    1KA

    1KA

    Voltage protection level at 4kV( 1.2/50µS)

    Up

    25V(line/line)     

    ≤800V(line/PG,SG/PG)

    ≤25V(line/SG)

    60V(line/line)     

    ≤800V(line/PG,SG/PG)

    ≤60V(line/SG)

    Response time

    tA

    ≤4ns(line/line)    

    ≤20ns(line/PG,SG/PG)

    ≤4ns(line/SG)

    ≤4ns(line/line)    

    ≤20ns(line/PG,SG/PG)

    ≤4ns(line/SG)

    Max. load current

    IN

    100mA

    400mA

    Series impedance per line

    R

    1.5Ω

    Capacitance

    C

    ≤300pF(line/line)   

    ≤100pF(line/PG,SG/PG)

    ≤300pF(line/SG)

    ≤1500pF(line/line)   

    ≤100pF(line/PG,SG/PG)

    ≤1500pF(line/SG)

    Operating temperature range

     

    -40°C...+80°C

    Cross-sectional area

     

    Max. 2.5m m2  flexible

    Mounting on

     

    35mm DIN rail

    Enclosure material

     

    Orange thermoplastic material, UL94-V0          

    Standards

     

    IEC 61643-21 & GB 18802.21

    Certification

     

    CE (LVD, EMC)

     MAIN CHARACTER 

    1, Small size, only 7mm wide module

    2, Connected to earth by DIN rail or earthing terminal

    3, With shield terminal(direct or indirect to earth)

    INSTALLATION INSTRUCTION 

    1. This data surge arrester is connected in series to the protected device.

    2. The IN (1/2, 3/4) terminal should be connected to the single lines input, the OUT (5/6, 7/8) terminal should be connected to the protected devices.

    3. There is a earthing terminal in each side, and it is recommended to use the one at output side; earth lead must be connected to the earthing system, ideally using 2.5mm²  cable. The cable should be as short as possible.

    4. After above, you should ensure the circuit is functioning.

    Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replacethe SPD.

    TS-SD5 INSTALLATION DIAGRAM 

    TS-SD5-Data-Surge-Arrester-Widely-Used

     

    TS-SD5-Data-Surge-Arrester-For-sale

     

    TS-SD5-Data-Surge-Arrester-Cheap

    WARNING:  

    1, The device must be installed by electrically skilled person, conforming to national standards and 

      safety regulations. 

    2, It is recommended that installation should be done under power off condition.