• Product Name :

    TS-SP24 Information Surge Protector

  • Instruction

    ♦ TS-SP Signal Line Surge Protection Device for Information Technology System 

    INTRODUCTIONTS-SP series information surge protector is designed according to IEC 61643-21; GB 18802.21; YD/T 1542. and at LPZ 0A -2 or higher, or directly at the upstream near the protected devices Provide protection for 2 single wires of unbalanced interfaces for measured and controlled system. 

    ♦ Mainly used in lightning protection for measuring and controlling system. such as the field bus, PLC, input/output interface of the 0-20mA, 4-20mA, Analog Signal, PLC, RS485 / RS422, CAN BUS, Modbus, Profibus.... control line. (TS-SP110 could also be used for telecommunications, telephone line,ADSL/ISDN line).

    ♦ CUSTOM-MADE CIRCUIT、Voltage & Technical Data AVAILABLE

    Similar/Related Products

    TS-SP24-Information-Surge-Protector-Good-Quality

    TS-SP24-Information-Surge-Protector-High-Efficiency

    Packing of TS-SP Series Control Surge Protector

    TS-SP24-Information-Surge-Protector-Warranty

    TS-SP24-Information-Surge-Protector-High-Efficiency

    ♦ Product Size of TS-SP Series Surge Protective Device

    TS-SP24-Information-Surge-Protector-Low-Price


    ♦ Basic Circuit Diagram (TS-SP5 ~ TS-SP60)

    TS-SP24-Information-Surge-Protector-Factory

    ♦ Technical Data 

    Model       

     

    TS-SP5 

    TS-SP12 

    TS-SP24 

    TS-SP48 

    TS-SP60 

    TS-SP110 

    Nominal voltage

    Un

    5V

    12V

    24V

    48V

    60V

    110V

    Rated voltage

    (max. continuous voltage)

    Uc

    6V-/ 4.2V~

    14V-/ 10V~

    26V-/ 19V~

    55V-/

    39V~

    65V- /

     50V~

    170V-/ 130V~

    Nominal current

    IL

    0.5A

    0.5A

    0.5A

    0.5A

    0.5A

    1A

    Lightning discharge current (10/350)

    Iimp 

    2.5kA (per line)

    5kA (total)

    Nominal discharge current (8/20)

    In

    10kA (per line

    20kA (total)

    Voltage protection level at Iimp

    Up

    ≤30V (line-line) 

    ≤17V (line-PG)

    ≤60V(line-line) 

    ≤30V(line-PG)

    ≤90V(line-line)

    ≤45V(line-PG)

    ≤150V (line-line) 

    ≤75V (line-PG)

    ≤200V (line-line)

    ≤100V (line-PG)

    ≤600V (line-line) 

    ≤300V (line-PG)

    Response time

    tA

    ≤1ns(line-line)

    ≤1ns(line-PG) 

    ≤1ns(line-line)

    ≤1ns (line-PG)

    ≤1ns(line-line)

    ≤1ns (line-PG)

    ≤1ns(line-line)

    ≤1ns (line-PG)

    ≤1ns(line-line)

    ≤1ns (line-PG)

    25ns(line-line)

    25ns(line-PG)

    Bandwidth

    fG

    1.6MHz

    (AD-PG)

    2.9MHz (AD-PG)

    5.1MHz

    (AD-PG)

    8.5MHz (AD-PG)

    10.8MHz

    (AD-PG)

    24.0MHz

    (AD-PG)

    Series impedance per line

    R

    1.4 Ω

    1.9 Ω

    2.2 Ω

    2.2 Ω

    2.2 Ω

    0.4 Ω

    Capacitance

    C

    3nF (line-line)

    5nF (line-PG)

    1nF (line-line)

    2nF (line-PG)

    0.7nF(line-line) 

    1.3nF(line-PG)

    0.3nF(line-line)

    0.6nF (line-PG)

    0.3nF (line-line)

    0.6nF (line-PG)

    0.2nF(line-line)

    1.4nF (line-PG)

    Operating temperature range

     

    -40°C...+80°C

    Relative humidity

     

    ≤95% (25°C)

    Cross-sectional area

     

    Max. 2.5mm2 flexible

    Mounting on

     

    35mm DIN rail

    Enclosure material

     

    Yellow thermoplastic, UL94-V0

    Standards

     

    IEC 61643-21; GB 18802.21; YD/T 1542

    Certification

     

    CE (LVD, EMC)

     MAIN CHARACTER 

    1, Composed by two parts: the base and the protection module

    2, The signal will not be disconnected when replacing the module

    3, High discharge capacity, low voltage protection level

    4, Option without GDT or with GDT BASE part

    INSTALLATION INSTRUCTION 

    1. The signal lightning arrester is connected in series to the protected device.

    2. Mount the SPD on the 35 mm DIN rail.

    3. The out terminal should be connected to the protected devices.

    4. There is a earthing terminal in each side, and it is recommended to use the one at output side; earth lead must be connected to the earthing system, ideally using 2.5mm²cable. The cable should be as short as possible.

    5. After above, you should ensure the circuit is functioning.

    Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replacethe SPD. 

    TS-SP Series Surge Arrester INSTALLATION DIAGRAM

    TS-SP24-Information-Surge-Protector-Professional-Manufacturer

     

    TS-SP24-Information-Surge-Protector-Widely-Used

    WARNING:  

    1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 

    2. It is recommended that installation should be done under power off condition.