Communication Surge Arrester
Home » Lightning Products » IT Surge Protection » Communication Surge Arrester
TS-TAI110 Telephone Line Surge Arrester
Next : TS-TAIRJ11 Surge Protector
Instruction
♦ TS-TAI110 Telephone Line Surge Arrester is designed according to IEC 61643-21; GB 18802.21; YD/T 1542. and at LPZ 0A -2 or higher, especially used for telephone line,ADSL line and ISDN line.
♦ Product Size
♦ Basic Circuit Diagram
♦ Technical Data of TS-SP110 (equal to TS-TAI110)
Model |
|
TS-TAI110 |
Nominal voltage |
Un |
110V |
Rated voltage (max. continuous voltage) |
Uc |
170V-/ 130V~ |
Nominal current |
IL |
1A |
Lightning discharge current (10/350) |
Iimp |
2.5kA (per line) 5kA (total) |
Nominal discharge current (8/20) |
In |
10kA (per line 20kA (total) |
Voltage protection level at Iimp |
Up |
≤600V (line-line) ≤300V (line-PG) |
Response time |
tA |
25ns(line-line) 25ns(line-PG) |
Bandwidth |
fG |
24.0MHz (AD-PG) |
Series impedance per line |
R |
0.4 Ω |
Capacitance |
C |
0.2nF(line-line) 1.4nF (line-PG) |
Operating temperature range |
|
-40°C...+80°C |
Relative humidity |
|
≤95% (25°C) |
Cross-sectional area |
|
Max. 2.5mm2 flexible |
Mounting on |
|
35mm DIN rail |
Enclosure material |
|
Yellow thermoplastic, UL94-V0 |
Standards |
|
IEC 61643-21; GB 18802.21; YD/T 1542 |
Certification |
|
CE (LVD, EMC) |
♦ MAIN CHARACTER
1, Composed by two parts: the base and the protection module
2, The signal will not be disconnected when replacing the module
3, High discharge capacity, low voltage protection level
INSTALLATION INSTRUCTION 1. This telephone surge arrester is connected in series to the protected device. 2. Mount the telephone surge arrester on the 35 mm DIN rail. 3. The out terminal should be connected to the protected devices. 4. There is a earthing terminal in each side, and it is recommended to use the one at output side; earth lead must be connected to the earthing system, ideally using 2.5mm² cable. The cable should be as short as possible. 5. After above, you should ensure the circuit is functioning. Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replacethe telephone surge arrester. |
INSTALLATION DIAGRAM
|
WARNING: 1, The device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2, It is recommended that installation should be done under power off condition. |