• Product Name :

    12V / 24V / 48V / 110V / 220V / 380V DC Surge Protection Device for PV / DC Power Supply System

  • Instruction

    TSTLP® 12Vdc ~ 385Vdc Type 2 Surge Protection Device  is designed according to IEC61643-11, EN 61643-11 & GB/T 18802.11. standards for installation at LPZ0B-1 or higher, protecting voltage equipment from surge.Applied in modular SPD Class (Class C) for DC power supply system & PV DC power supply system such as telecommunication room, microwave, communication room & so on...

    ♦ Relative T1+2 / T2 SPD for DC / PV Power Supply System

    12V- -24V- -48V- -110V- -220V- -380V-DC-Surge-Protection-Device-for-PV- -DC-Power-Supply-System-Professional

    ♦ Dimension(mm)

    12V- -24V- -48V- -110V- -220V- -380V-DC-Surge-Protection-Device-for-PV- -DC-Power-Supply-System-Professional

    ♦ Technical Data 

    Model Nr 

     

    TS-M10RM 

    TS-24M10RM 

    TS-48M15RM 

    TS-M20RM 

    TS-275M20RM 

    TS-XM20RM 

    Nominal d.c.voltage

    Un

    12V-

    24V-

    48V-

    110V-

    220V-

    385V-

    Rated voltage (max.contnuous d.c.voltage)

    Uc

    38V-

    56V-

    85V-

    170V-

    275V-

    505V-

    Nominal discharge current (8/20)

    ln

    10kA

    10kA

    15kA

    20kA

    20kA

    20kA

    Max.discharge current (8/20)

    Imax

    20kA

    20kA

    30kA

    40kA

    40kA

    40kA

    Total discharge current (8/20)

    Itotal

    40kA

    40kA

    60kA

    30kA

    80kA

    80kA

    Voltage protection level at In

    Up

    ≤200V

    ≤300V

    ≤400V

    ≤700V

    ≤900V

    ≤1.8kV

    Voltage protection level at 3kA

    Up

    ≤150V

    ≤210V

    ≤320V

    ≤580V

    ≤690V

    ≤1.35V

    Response time

    tA

    ≤25ns

    ≤25ns

    ≤25ns

    ≤25ns

    ≤25ns

    ≤25ns

    Max.back up fuse

    F

    35A gL/gG

    35A gL/gG

    35A gL/gG

    35A gLgG

    35AgLgG

    35AgLgG

    Operating temperature range

    Tu

    -40℃...+80℃

    Cross-section area (L/N)

     

    1.5mm²~10mm²solid/flexible

    Cross-section area(PE)

     

    6.0mm²~25mm²solid/flexible

    Mounting on

     

    35mm DIN rail

    Enclosure material

     

    Light Grey Thermoplastic,UL94-V0

    Dimension

     

    1 mod

    Test standards

     

    IEC 61643-11;EN 64643-11;GB/T 18802.11

    Compliant

     

    CE

    Type of remote signalling contact

     

    Switching contact

    Switching capacity

    Un / In

    AC:250V/0.5A  DC:250V/0.1A,125V/0.2A,75V/0.5A

    Cross-sectional area for remote signalling contact

     

    Max.1.5mm²solid  /flexible

     

    ♦ Features 

    1- Combined DC SPD,slim 18mm form factor

    2- Pluggable module, easy for installation & maintenance, high discharge capacity,quick response

    3- Double thermal disconnector device,providing more reliable protection

    4- Multifunctional terminal for connecting conductors & busbars

    5-Windows will change to red when fault & also provide remote alarm control at the same time 

     

    ♦ INSTALLATION INSTRUCTION

    According to lightning protection zones concept, for installation at LPZ 0B-1 or higher. This surge protection is usually installed in distribution-box or feeder bus of UPS,protecting devices or equipment downstream.Fuse must be installed at the upstream of the SPD or the lightning protector to make sure that protected system has double protection. The value of the fuse used in a SPD system should be confirmed to:

    1. The value of FUSE should not be larger than the max.withstand capacity of the SPD's backup fuse value.

    2. Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.

    Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of SPD.

     

    ♦ INSTALLATION STEPS

    1) Check the product for integrity of the package; make sure the product window indicate green.

    2) Mount the SPD on the 35mm DIN rail.

    3) Connect conductors, the cross-section area of cable must be larger than 6mm2 . The withstand voltage value of cable is not smaller than AC500V; ensure wiring reliable.

    4) If need remote alarm, it should be connected signal lines to remote signal terminal 1 and 2, or 2 and 3 (When normal,1 and 2 open, 2 and 3 close; when fault, the state is reversed).

    1) After above, switch on the power supply and turn on the circuit breaker,if  the SPD’s window  does  not appear red, this indicates the unit is operating normally.

    Regularly inspect the operating status, especially after lightning. Once the fuse upstream break, or the SPD's window indicates red, electrician should check/replace the SPD.

     

    ♦ INSTALLATION DIAGRAM FOR REFERENCE

    12V- -24V- -48V- -110V- -220V- -380V-DC-Surge-Protection-Device-for-PV- -DC-Power-Supply-System-High-Efficiency

     

    ♦ WARNING: 

    1- The device must be installed by electrically skilled person, conforming to national standards and safety regulations.

    2- It is recommended that installation should be done under power off condition.